LED Lighting for Indoor Riding Arenas and Outdoor Equestrian Arenas

Lighting an equestrian area is not simply about achieving a certain number of lux. Layout, uniformity, glare, contrasts, mounting height and optics must be studied to ensure good visibility for the rider while creating a consistent lighting environment for the horse.

200 to 500 lux Indoor riding arena
100 to 500 lux Outdoor equestrian arena
0.50 to 0.70 Uniformity Emin / Eavg
Photometric study Before sizing
LED lighting in an indoor riding arena with rider and horse
Indoor riding arena
LED lighting for an outdoor equestrian arena mounted on poles
Outdoor equestrian arena

Understanding the requirements

Lighting designed for the riding area, the rider and the horse

A 20 × 40 m indoor arena, a 20 × 60 m indoor arena and a 40 × 80 m outdoor equestrian arena cannot be studied in the same way.

Dimensions, available height, roof structure or poles, the discipline practised and the required lighting level directly affect the number of luminaires, their power, optics and orientation.

STADÉLUM sizes the solution according to the site: required average lighting level, uniformity, layout, visual comfort, glare control and the power actually required.

Riding area dimensions

Indoor riding arena or outdoor arena: very different surface areas

The dimensions below are common formats or layout references. They do not replace the specific regulations applicable to the discipline and competition level concerned.

INDOOR

Indoor riding arenas

20 × 40 m · 800 m² 20 × 60 m · 1,200 m²

20 × 60 m is a standard indoor riding arena size. 20 × 40 m is also common for training and riding lessons.

Diagram showing the dimensions of 20 x 40 m and 20 x 60 m indoor riding arenas
OUTDOOR

Outdoor equestrian arenas

20 × 60 m · 1,200 m² 40 × 80 m · 3,200 m²

A dressage arena can be arranged over 20 × 60 m. A 40 × 80 m arena already represents 3,200 m² to illuminate and requires specific consideration of poles and optics.

Diagram showing the dimensions of 20 x 60 m and 40 x 80 m outdoor equestrian arenas

NF EN 12193 reference values

What lighting levels should be targeted for equestrian facilities?

The level must be selected according to the actual use of the facility. The objective is to achieve the right illuminance level with consistent distribution, rather than systematically installing the maximum possible power.

Target Indoor riding arena Uniformity Outdoor arena Uniformity
Class IIITraining / leisure 200 lux ≥ 0.50 100 lux ≥ 0.50
Class INational / international level 500 lux ≥ 0.70 500 lux ≥ 0.70

Values presented as design references. The specifications, discipline and competition level must be checked before defining the final photometric target.

Photometric study example · indoor

20 × 40 m indoor arena: 27 SUPRALED luminaires at 5.20 m

SIMULATION · NOT AN ON-SITE MEASUREMENT
27SUPRALED luminaires
5.20 mstudied height
75 Wsetting per luminaire
2.025 kWinstalled power
440 luxsimulated average
0.63simulated uniformity

What the study shows

Distributing 27 light points across three rows makes it possible to focus on uniformity rather than concentrating all the power into just a few luminaires.

With an average of 440 lux and U0 = 0.63, this simulation exceeds the Class II horizontal criteria of 300 lux and 0.60.

Photometric study of a 20 x 40 m indoor riding arena with SUPRALED luminaires
Photometric simulation example — 20 × 40 m indoor riding arena.

Photometric study example · outdoor

40 × 80 m arena: 12 SMASH floodlights on four 13 m poles

SIMULATION · NOT AN ON-SITE MEASUREMENT
12SMASH floodlights
4 polesperimeter layout
13 mphotometric height
5.2 kWtotal power
100 luxsimulated average
0.50simulated uniformity

Studied configuration

Eight 500 W SMASH and four 300 W SMASH floodlights are distributed across four poles. The simulated result of 100 lux average with U0 = 0.50 corresponds to a training / local-use target.

Photometric study of a 40 x 80 m outdoor equestrian arena with SMASH floodlights
Photometric simulation example — 40 × 80 m outdoor arena.

Layout

At what height should the luminaires be installed?

Indoor riding arena

5.20 m

in the example study presented

The height must be checked against the available clearance, roof structure, equipment and riders' lines of sight.

Outdoor equestrian arena

13 m

in the 40 × 80 m photometric study

This photometric height must then be made compatible with a pole, crossarm, windage and foundation actually sized for the site.

CONICA 20000 tapered cylindrical pole for outdoor lighting CONICA · CONIMAST

Outdoor installation structure

CONICA poles for outdoor equestrian arena lighting

For an outdoor arena, the study does not stop at selecting the floodlight. STADÉLUM can study the integration of CONICA tapered cylindrical poles from CONIMAST when they are compatible with the height, floodlights and mechanical constraints of the project.

Sizing must take into account the support height, number and weight of the floodlights, crossarm, surface area exposed to wind, the site's wind zone and the foundation block.

Important point for the 40 × 80 m example: the simulation uses a photometric height of 13 m. The documented CONICA 20000 range must be checked separately to confirm that a support solution is available and mechanically suitable for this height.

View the CONICA pole range

Calculation and verification

What calculation grid should be used for an equestrian photometric study?

It is not relevant to give a single number of points applicable to every installation: the grid depends on the discipline, reference area and the dimensions actually being studied.

INDOOR · JUMPING 60 × 40 m

17 × 11

187 points
INDOOR · DRESSAGE 70 × 30 m

19 × 9

171 points
OUTDOOR · JUMPING 110 × 55 m

21 × 11

231 points
OUTDOOR · DRESSAGE 65 × 25 m

17 × 7

119 points

These dimensions are photometric references. For a 20 × 40 m indoor arena or a 40 × 80 m outdoor arena, the grid must be adapted to the dimensions actually being studied.

Rider and horse jumping an obstacle

Visual comfort

Lighting for the rider… but also for the horse

A high-quality installation should avoid sudden changes in brightness, pronounced shadow areas and light sources that are too visible along movement paths.

Limit abrupt light / dark transitions Avoid harsh light sources along movement paths Maintain good visibility of the ground and obstacles Aim for even light distribution

STADÉLUM solutions

Which luminaires should be considered for an equestrian centre?

The product is selected after studying the height, layout, optics and required lighting level. Power alone is not enough to correctly size an equestrian facility.

COURTLINE linear LED sports luminaire
INDOOR ARENA · DEPENDING ON STUDY

COURTLINE

An alternative to consider when the roof structure or mounting points are compatible with its light distribution.

  • 240 W or 320 W
  • 4000 K or 5000 K
  • 110° × 60° optic
  • ±15° tilt
View COURTLINE
SMASH LED floodlight for outdoor sports lighting
OUTDOOR ARENA

SMASH

The solution studied in our 40 × 80 m example, combining 300 W and 500 W versions across four poles.

  • 300 W or 500 W
  • 4000 K or 5000 K
  • 110° × 60° optic
  • Pole mounting bracket available
View SMASH
ARENA LED floodlight for large equestrian arenas and outdoor sports lighting
LARGE OUTDOOR ARENA

ARENA

To be considered when the surface area, support height or required lighting level requires higher luminous flux.

  • 600 to 1800 W
  • Dedicated sports optics
  • Integrated DALI
  • Anti-glare visor available
View ARENA

Colour temperature

4000 K: a relevant choice for many projects

For many indoor and outdoor equestrian arenas, neutral white light around 4000 K provides a consistent starting point when the product range and environmental constraints allow it.

Design

Points to check before choosing the floodlights

Uniformity

Limit differences between bright and dark areas.

Glare

Control viewing directions for both rider and horse.

Optics

Direct light towards the riding area rather than oversizing the installation.

Poles

Combine photometric height with mechanical sizing.

Roof structure

Check positions, structure and accessibility indoors.

Dust / watering

Provide protection and maintenance suitable for the equestrian environment.

Power

Optimise installed power based on the calculated result.

Spill light

Control light directed towards neighbouring properties and the environment.

FAQ

Frequently asked questions about equestrian lighting

How many lux are required in an indoor riding arena?

The reference values presented on this page are 200, 300 and 500 lux depending on the lighting class and intended use.

How many lux are required for an outdoor equestrian arena?

The reference values presented are 100, 200 and 500 lux. Uniformity and glare must also be controlled.

Can CONICA poles be used for an outdoor equestrian arena?

Yes, provided that the height, windage, floodlights, crossarm and foundation are checked. The pole reference should not be selected based solely on photometric height.

Why carry out a photometric study before ordering?

It makes it possible to check the average level, uniformity, aiming directions, optics, number of luminaires and required power before finalising the project.