STADÉLUM · EUROPEAN STANDARD
EN 12193: lighting levels for sports facilities
The European standard EN 12193:2018 defines minimum requirements for the artificial lighting of the main indoor and outdoor sports facilities.
Below is a summary of the requirements for maintained horizontal illuminance, uniformity, glare limitation and colour rendering according to lighting Classes I, II and III.
Understanding EN 12193
The required lux level depends on the sport and lighting class
There is no single “EN 12193” value that applies to every sports facility.
The standard associates each sport with a reference area, a calculation grid and specific lighting performance requirements. A football pitch, a tennis court and an equestrian arena therefore do not necessarily have the same values for the same lighting class.
Reference areas
Principal Area and Total Area
The standard distinguishes in particular between the Principal Area (PA), corresponding to the main area required for practising the sport, and the Total Area (TA), which generally includes the PA and an additional safety area.
The dimensions and grid points depend directly on the sport being studied.
Lighting classes
The three classes used by EN 12193
High-level competitions and high-level training, particularly where viewing conditions are demanding.
Intermediate-level competitions and training requiring good visual performance.
Lower-level competitions, general training, school sports and recreational use.
Class I does not automatically mean “national” and Class II does not automatically mean “regional”. Sports federations may use their own classification systems.
EN 12193:2018 · outdoor
Outdoor sports facilities
Ēm = maintained average horizontal illuminance · U0 = Emin / Eavg · GR = Glare Rating · Ra = colour rendering index.
| Sport | Class | Maintained Ēm | Uniformity U0 | GR max. | Ra min. |
|---|---|---|---|---|---|
| Athletics | I | 500 lux | 0.70 | 50 | 70 |
| II | 200 lux | 0.50 | 50 | 60 | |
| III | 100 lux | 0.50 | 55 | 60 | |
| Equestrian Outdoor jumping / dressage | I | 500 lux | 0.70 | 50 | 70 |
| II | 200 lux | 0.50 | 50 | 60 | |
| III | 100 lux | 0.50 | 55 | 60 | |
| Outdoor tennis | I | 500 lux | 0.70 | 50 | 70 |
| II | 300 lux | 0.70 | 50 | 60 | |
| III | 200 lux | 0.60 | 55 | 60 | |
| Outdoor padel | I | 500 lux | 0.70 | 50 | 70 |
| II | 300 lux | 0.70 | 50 | 60 | |
| III | 200 lux | 0.60 | 55 | 60 | |
| Football | I | 500 lux | 0.70 | 55 | 70 |
| II | 200 lux | 0.60 | 55 | 60 | |
| III | 75 lux | 0.50 | 55 | 60 | |
| Rugby | I | 500 lux | 0.70 | 55 | 70 |
| II | 200 lux | 0.60 | 55 | 60 | |
| III | 75 lux | 0.50 | 55 | 60 | |
| Outdoor basketball | I | 500 lux | 0.70 | 55 | 70 |
| II | 200 lux | 0.60 | 55 | 60 | |
| III | 75 lux | 0.50 | 55 | 60 | |
| Outdoor handball | I | 500 lux | 0.70 | 55 | 70 |
| II | 200 lux | 0.60 | 55 | 60 | |
| III | 75 lux | 0.50 | 55 | 60 | |
| Outdoor volleyball | I | 500 lux | 0.70 | 55 | 70 |
| II | 200 lux | 0.60 | 55 | 60 | |
| III | 75 lux | 0.50 | 55 | 60 |
EN 12193:2018 · indoor
Sports halls and indoor sports facilities
Values differ depending on the sport category, particularly for racket sports.
| Sport | Class | Maintained Ēm | Uniformity U0 | GR max. | Ra min. |
|---|---|---|---|---|---|
| Badminton | I | 750 lux | 0.70 | 35* | 80 |
| II | 500 lux | 0.70 | 40* | 60 | |
| III | 300 lux | 0.70 | 40* | 60 | |
| Table tennis | I | 750 lux | 0.70 | 35* | 80 |
| II | 500 lux | 0.70 | 40* | 60 | |
| III | 300 lux | 0.70 | 40* | 60 | |
| Basketball | I | 750 lux | 0.70 | 35* | 80 |
| II | 500 lux | 0.70 | 40* | 60 | |
| III | 200 lux | 0.50 | 40* | 60 | |
| Handball | I | 750 lux | 0.70 | 35* | 80 |
| II | 500 lux | 0.70 | 40* | 60 | |
| III | 200 lux | 0.50 | 40* | 60 | |
| Volleyball | I | 750 lux | 0.70 | 35* | 80 |
| II | 500 lux | 0.70 | 40* | 60 | |
| III | 200 lux | 0.50 | 40* | 60 | |
| 5-a-side / 6-a-side football Indoor / futsal | I | 750 lux | 0.70 | 35* | 80 |
| II | 500 lux | 0.70 | 40* | 60 | |
| III | 200 lux | 0.50 | 40* | 60 | |
| Indoor tennis | I | 750 lux | 0.70 | 35* | 80 |
| II | 500 lux | 0.70 | 40* | 60 | |
| III | 300 lux | 0.50 | 40* | 60 | |
| Indoor padel | I | 750 lux | 0.70 | 35* | 80 |
| II | 500 lux | 0.70 | 40* | 60 | |
| III | 300 lux | 0.50 | 40* | 60 | |
| Indoor equestrian Indoor arena | I | 500 lux | 0.70 | 35* | 80 |
| II | 300 lux | 0.60 | 40* | 60 | |
| III | 200 lux | 0.50 | 40* | 60 |
* For several indoor applications in these tables, the GR criterion applies in particular to mounting heights above 10 m. The full EN 12193 text should be consulted for the notes specific to each sport.
Multi-sport hall
A sports hall should not be assessed using a single generic value
When a sports hall contains several marked courts, EN 12193 provides for performance to be assessed on each sports area using the calculation grid corresponding to the relevant sport.
A sports hall study intended for badminton, basketball and volleyball should therefore verify that the installation is suitable for each of these uses.
Reading the tables
Four values to consider together
Average lux level to be maintained across the area being assessed.
Checks that the least illuminated areas remain consistent with the average.
An indicator intended to limit glare under the conditions defined by the standard.
Indicates how accurately colours are reproduced by the lighting.
An essential concept
The tables specify maintained values
The specified level is not simply the level a new installation should produce on its first day.
The design must take into account the ageing of the light sources, dirt accumulation on the luminaires, the environment and the maintenance strategy in order to maintain the required level over time.
STADÉLUM method
From an EN 12193 table to a real installation
The standard defines performance requirements. A photometric study determines how to achieve them on site.
Identify the sport
Determine the EN 12193 table and lighting class corresponding to the intended use.
Define the areas
Check the corresponding PA, TA, dimensions and calculation grid.
Analyse the site
Heights, poles, roof structure, available mounting positions and environmental constraints.
Select the optics
Distribute the useful luminous flux before increasing the number of luminaires or their power.
Check the results
Average lux, uniformity, GR, colour rendering and surrounding areas.
Optimise
Determine an installed power that is consistent with the required performance.
EN 12193 + SPORTS FEDERATIONS
What about your sport in France?
Sports federations may adopt EN 12193 values, supplement the standard or impose their own assessment methods.
EN 12193 PRELIMINARY STUDY
Which lighting level should be applied to your sports facility?
Before defining the number or power of the luminaires, STADÉLUM analyses the sport, the required lighting class, dimensions, height, layout and site constraints.
Request a preliminary studyThis page provides an educational summary of certain applications of EN 12193:2018 and does not reproduce the standard in full. The official text, its notes, reference area dimensions and any additional requirements must be checked for the project concerned.