LED Lighting for Padel Courts

Study Padel Lighting Before Choosing the Floodlights

Layout, height, optics, uniformity, reflections on the glass and installed power must all be studied together.

STADÉLUM prepares technical configurations for indoor and outdoor padel courts, taking into account the level of play, the site structure and players’ visual comfort.

Leisure and Training 300 lux
Competition 500 lux
Higher Level 750 lux
Study Grid 13 points

Three Calculated Configurations According to the Required Level

Leisure / Training Target 300 lux

Study provided with 4 COURTLINE 240 W floodlights. Simulated average illuminance: 415.5 lux. Emin/Eavg uniformity: 86%.

Competition Target 500 lux

Study provided with 4 COURTLINE 320 W floodlights. Simulated average illuminance: 577 lux. Emin/Eavg uniformity: 95%.

Higher-Level Target 750 lux

Study provided with 8 COURTLINE 240 W floodlights. Simulated average illuminance: 823.7 lux. Emin/Eavg uniformity: 92%.

All three results come from the supplied simulations using a 13-point grid. They are not measurements taken on site.

Check Light Distribution Across 13 Points

The average alone is not enough to assess the quality of an installation. The calculation points taken at ground level (except point 7, which is taken at net height) make it possible to check the areas close to the glass, the net and the back of the court.

The calculation must also check uniformity, aiming directions and areas sensitive to reflections or glare.

Average Illuminance Uniformity Optics Visual Comfort
123 456 7 8910 111213

Photometric Studies Provided for 300, 500 and 750 Lux

The three 3D views below correspond to the supplied calculation studies. The results are simulated across 13 points and must be distinguished from illuminance measurements taken after installation.

01
300 Lux Target

4 COURTLINE 240 W

3D photometric study of a padel court with four COURTLINE 240 W floodlights
3D Simulation — 4 × 240 W Configuration
Floodlights4 × COURTLINE 240 W
Installed Power960 W
Calculation Points13
Average Illuminance415.5 lux
Minimum Illuminance356 lux
Maximum Illuminance444 lux
Emin / Eavg 86% U0 = 0.86
Eavg / Emax 94% calculated ratio

Simulated result from the supplied calculation study

02
500 Lux Target

4 COURTLINE 320 W

3D photometric study of a padel court with four COURTLINE 320 W floodlights
3D Simulation — 4 × 320 W Configuration
Floodlights4 × COURTLINE 320 W
Installed Power1,280 W
Calculation Points13
Average Illuminance577 lux
Minimum Illuminance548 lux
Maximum Illuminance630 lux
Emin / Eavg 95% U0 = 0.95
Eavg / Emax 92% calculated ratio

Simulated result from the supplied calculation study

03
750 Lux Target

8 COURTLINE 240 W

3D photometric study of a padel court with eight COURTLINE 240 W floodlights
3D Simulation — 8 × 240 W Configuration
Floodlights8 × COURTLINE 240 W
Installed Power1,920 W
Calculation Points13
Average Illuminance823.7 lux
Minimum Illuminance759 lux
Maximum Illuminance924 lux
Emin / Eavg 92% U0 = 0.92
Eavg / Emax 89% calculated ratio

Simulated result from the supplied calculation study

Understanding the Results: all three configurations exceed their nominal target in the supplied simulations. The final choice must nevertheless take into account the site, glazing, height, optics, aiming and installed power.
Supplied Calculation Studies

Detailed Results Across the 13 Points

The values are reproduced as they appear in the supplied table. They make it possible to check the average, minimum, maximum and the two uniformity ratios.

Show the Values for the 13 Points 300 Lux / 500 Lux / 750 Lux Comparison
Point 300 Lux Configuration
4 × COURTLINE 240 W
500 Lux Configuration
4 × COURTLINE 320 W
750 Lux Configuration
8 × COURTLINE 240 W
1414 lux558 lux759 lux
2432 lux581 lux790 lux
3441 lux575 lux840 lux
4390 lux553 lux785 lux
5438 lux614 lux884 lux
6410 lux566 lux824 lux
7356 lux630 lux924 lux
8398 lux562 lux812 lux
9444 lux617 lux886 lux
10390 lux548 lux795 lux
11432 lux567 lux802 lux
12434 lux578 lux823 lux
13422 lux552 lux784 lux
Eavg415.5 lux577 lux823.7 lux
Emin / Eavg86%95%92%
Eavg / Emax94%92%89%
300 Lux — Calculated Range 356 to 444 lux average 415.5 lux
500 Lux — Calculated Range 548 to 630 lux average 577 lux
750 Lux — Calculated Range 759 to 924 lux average 823.7 lux

Technical Comparison of the Three Padel Lighting Levels

Specifications 300 Lux Target Study 500 Lux Target Study 750 Lux Target Study
StatusSupplied calculation studySupplied calculation studySupplied calculation study
Floodlights4 × COURTLINE 240 W4 × COURTLINE 320 W8 × COURTLINE 240 W
Installed Power960 W1,280 W1,920 W
Calculation Grid13 points13 points13 points
Simulated Average Illuminance415.5 lux577 lux823.7 lux
Minimum Illuminance356 lux548 lux759 lux
Maximum Illuminance444 lux630 lux924 lux
Emin / Eavg86%95%92%
Eavg / Emax94%92%89%

The results in all three columns are simulations from the supplied calculation studies. They are not measurements taken after installation.

Indoor and Outdoor Padel: Two Different Technical Environments

Indoor padel court studied by STADÉLUM

Indoor Padel

Clear height, roof structure, glazing and reflections influence floodlight positioning. The solution must preserve ball visibility without creating discomfort during high trajectories.

Points to Check: available height, mounting on the roof structure, glazing, reflections, optics and access for aiming adjustments.
Outdoor padel court with lighting poles

Outdoor Padel

The project must coordinate poles, wind, setbacks, glazing, neighbouring properties and spill light. A moderate mounting height may lead to consideration of the CONICA range, subject to the loads and selected layout.

The pole is not selected based on height alone: the weight and windage area (Scx) of the floodlights, crossbar, wind conditions and site conditions must also be checked.

Why Entrust Your Padel Lighting Study to STADÉLUM?

01

Site Analysis

Dimensions, height, glazing, surroundings, wind and installation constraints.

02

Photometric Study

13-point calculation, average lux, uniformity and sensitive areas.

03

Optics Selection

Light distribution adapted to the required throw and reduction of reflections.

04

Visual Comfort

Aiming directions studied according to ball trajectories and players.

05

Optimised Power

Installed power adjusted to the actual requirements of the project.

06

Coordinated Structure

Poles, supports and floodlights checked as a complete system.

Designing LED Lighting Suitable for Padel

Padel combines a compact playing area, glazing and high ball trajectories. The supplied calculation studies show three COURTLINE configurations: 4 × 240 W, 4 × 320 W and 8 × 240 W depending on the required level. Luminaire positioning remains essential for uniformity, visual comfort and control of installed power.

Indoors

The roof structure and clear height determine the available positions. The luminaires must remain compatible with overhead play and limit reflections visible on the glass walls.

Outdoors

Poles and supports must be coordinated with wind conditions, neighbouring properties, setbacks and the aiming directions defined by the calculation. The CONICA pole may be considered when its height range and load capacity are suitable for the selected configuration.

FAQ — LED Lighting for Padel Courts

What Lux Level Should Be Used for Padel?

The targets used on this page are 300 lux for leisure and training, 500 lux for competition and 750 lux for a higher level. The final level must correspond to the project requirements.

Why Calculate Lighting Across 13 Points?

This grid makes it possible to check light distribution across the entire court and compare the average illuminance with the least illuminated areas.

Can the Same Lighting Be Used Indoors and Outdoors?

No. Indoor installations involve height, roof structure and reflection constraints. Outdoor installations add poles, wind, neighbouring properties and spill light.

Is the CONICA Pole Suitable for Outdoor Padel?

It can be considered for certain configurations with moderate mounting heights. Compatibility depends on the floodlights, supports, wind conditions, total weight and exposed surface area.

What Results Do the Three Supplied COURTLINE Studies Achieve?

The 4 × 240 W configuration achieves an average of 415.5 lux with U0 = 0.86. The 4 × 320 W configuration achieves 577 lux with U0 = 0.95. The 8 × 240 W configuration achieves 823.7 lux with U0 = 0.92. These values are simulated.

What Is the Total Installed Power for Each Configuration?

The 300 lux configuration represents 960 W of installed power. The 500 lux configuration represents 1,280 W. The 750 lux configuration represents 1,920 W.

Do These Configurations Correspond to Completed Installations?

No. This page presents typical studies and technical targets. It does not claim any published STADÉLUM padel installation.

Padel Lighting Preliminary Study

Study the Court Before Pricing the Equipment

Send us the dimensions, indoor or outdoor context, available height, proposed layout and required illuminance level.

Request a Preliminary Study